TRANSFORMER BUSHINGS |
|
|
|
|
|
|
|
|
| STANDARD PARTICULARS | |||||
| Product No. |
BCPL 1101 |
BCPL 1102 |
BCPL 1103 |
BCPL 1104 |
|
| Ratings |
12 kV/ 250 Amp |
12 kV/400 630 Amp |
12 kV/ 1000 Amp |
12 kV/ 2000-3150 Amp |
|
|
Power Frequency One minute |
Dry, kVRms | 50 | 50 | 50 | 50 |
| WithstandVoltage |
Wet, kVRms |
45 | 45 | 45 | 45 |
| Impulse Withstand Voltage, kVp | 95 | 95 | 95 | 95 | |
STANDARD SPECIFICATIONS : IS 3347 Part III/Sec 1& IS 2099 & IEC-233
|
|
|
|
|
|
|
|
| STANDARD PARTICULARS | ||||||
| Product No. | BCPL-2201 | BCPL-2202 | BCPL-2203 | BCPL-2204 | ||
| Ratings |
24 kV/ 250 Amp |
24 kV/400 630 Amp |
24 kV/ 1000 Amp |
24 kV/2000 3150 Amp |
||
| Dimensions | A | mm | 145 | 155 | 175 | 190 |
| B | mm | 150 | 160 | 180 | 200 | |
| C | mm | 155 | 165 | 185 | 210 | |
| D | mm Min | 32 | 39 | 58 | 74 | |
| E | mm Max | 111 | 128 | 163 | 183 | |
|
Product Frequency One Minute Withstand Voltage |
Dry, kV | 60 | 60 | 60 | 60 | |
| Wet, kV | 55 | 55 | 55 | 55 | ||
| Impulse Withstand Voltage, kVp | 125 | 125 | 125 | 125 | ||
STANDARD SPECIFICATIONS : IS 3347 Part 4/Sec 1 & IS 2099 & IEC-233
|
|
|
|
|
|
|
| STANDARD PARTICULARS | |||||
| Product No. |
BCPL 3302 |
BCPL 3303 |
BCPL 3304 |
BCPL 3305 |
|
| Ratings |
36 kV/250 Amp |
36 kV/400- 630 Amp |
36 kV/1000 Amp |
36 kV/2000-3150 Amp |
|
| Visible Discharge Voltage, kV | 27 | 27 | 27 | 27 | |
|
Power Frequency One Minute Withstand Voltage |
Dry kV | 80 | 80 | 80 | 80 |
| Wet kV | 75 | 80 | 80 | 80 | |
| Impulse Withstand Voltage, kVp | 180 | 180 | 180 | 180 | |
STANDARD SPECIFICATIONS : IS 3347 Part V/Sec 1 & IS 2099 & IEC-233
|
|
|
| STANDARD PARTICULARS | ||||||||||||
| Product No. | BCPL-0101 | BCPL-0102 | BCPL-0103 | BCPL-0104 | BCPL-0105 | |||||||
| Ratings | 1.1 kV/250 Amp | 1.1 kV/400,630 Amp | 1.1 kV/1000 Amp | 1.1 kV/2000 Amp | 1.1 kV/3150 Amp | |||||||
| Part | I | II | I | II | I | II | I | II | I | II | ||
| Dimensions | A | mm | 50 | 60 | 70 | 85 | 90 | 110 | 104 | 125 | 125 | 150 |
| B | mm min | 14 | 20 | 22 | 28 | 32 | 37 | 44 | 51 | 50 | 61 | |
| C | mm | 70 | 30 | 80 | 30 | 85 | 35 | 85 | 35 | 85 | 35 | |
| D | mm | 45 | 50 | 55 | 70 | 55 | 90 | 55 | 104 | 55 | 125 | |
| E | mm | 27 | 26 | 43 | 41 | 53 | 46 | 66 | 64 | 86 | 80 | |
| F | mm | 34 | 30 | 49 | 46 | 67 | 57 | 82 | 70 | 100 | 90 | |
|
Power Frequency Withstand Voltage |
Dry kV | 12 | - | 12 | - | 12 | - | 12 | - | 12 | - | |
| Wet kV | 10 | - | 10 | - | 10 | - | 10 | - | 10 | - | ||
STANDARD SPECIFICATIONS : IS 3347 Part 1/Sec 1 & IS 7421& IEC-233
|
|
|
| STANDARD PARTICULARS | ||||||||||||
| Product No. | BCPL-0304 | BCPL-0305 | BCPL-0301 | BCPL-0302 | BCPL-0303 | |||||||
| Ratings | 3.6 kV/250 Amp | 3.6 kV/400, 630 Amp | 3.6 kV/1000 Amp | 3.6 kV/2000 Amp | 3.6 kV/3150 Amp | |||||||
| Part | I | II | I | II | I | II | I | II | I | II | ||
| Dimensions | A | mm | 75 | 70 | 90 | 85 | 110 | 110 | 125 | 125 | 145 | 150 |
| B | mm | 32 | 60 | 47 | 70 | 65 | 90 | 80 | 105 | 100 | 125 | |
| C | mm | 32 | 40 | 47 | 46 | 65 | 57 | 80 | 70 | 10 0 | 90 | |
| D | mm | 37 | 26 | 43 | 41 | 53 | 46 | 66 | 64 | 86 | 80 | |
| E | mm | 14 | 20 | 22 | 28 | 32 | 37 | 44 | 51 | 50 | 61 | |
| F | mm | 60 | - | 70 | - | 90 | - | 105 | - | 125 | - | |
|
Power Frequency Withstand Voltage |
Dry kV | 21 | - | 21 | - | 21 | - | 21 | - | 21 | - | |
| Wet kV | 21 | - | 21 | - | 21 | - | 21 | - | 21 | - | ||
| Impulse Withstand Voltage, kVp | 45 | - | 45 | - | 45 | - | 45 | - | 45 | - | ||
STANDARD SPECIFICATION : IS 3347 Part II/Sec 1 & 2099 & IEC -
233
BACK
Home | Cover Story | Company Profile | Clay Mines | Products Range | Manufacturing Process | Testing Phase | Clientele | Contact Us
Copyright © 2000 - 2003 ekhvaabs.
All Rights Reserved.
Revised: January 15, 2004
.
Site Conceived, Designed, Hosted and Maintained by ekhvaabs